4-wire DC inductive proximity switches : |
|
|
|
Group |
1 |
2 |
3 |
4 |
5 |
Hysteresis |
Sa |
(0,01 - 0,15) x Sn |
Switching frequency - slow (marked with the letter S) - fast (marked with the letter F) |
fT |
500 Hz 50 Hz 5 kHz |
200 Hz 50 Hz 1 kHz |
100 Hz 20 Hz 500 Hz |
200 Hz 50 Hz 800 Hz |
100 Hz 20 Hz 400 Hz |
Nominal voltage |
Un |
24 V |
Supply voltage |
Uc |
10 - 30 V |
Supply current |
Ic |
< 10 mA |
Output current |
Iz |
200 mA |
Ambient temperature range |
T |
-25°C... +70°C |
Protection standard (with cable/connector) |
|
IP 68 / IP 67 |
|
|
---|
Nominal sensing distance: |
2,5 mm |
Effective sensing distance: |
2 - 3 mm |
Housing: |
M 12 |
Material: | nickel plated brass |
Mounting: |
flush |
Group: |
1 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 126 315 | PSI 126 415 |
PNP | n.o. & n.c. | PSI 126 316 | PSI 126 416 |
|
|
|
---|
Nominal sensing distance: |
3,5 mm |
Effective sensing distance: |
3 - 4 mm |
Housing: |
M 12 |
Material: | nickel plated brass |
Mounting: |
non-flush |
Group: |
2 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 128 315 | PSI 128 415 |
PNP | n.o. & n.c. | PSI 128 316 | PSI 128 416 |
|
|
|
---|
Nominal sensing distance: |
5 mm |
Effective sensing distance: |
4 - 6 mm |
Housing: |
M 18 |
Material: | nickel plated brass |
Mounting: |
flush |
Group: |
2 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 186 315 | PSI 186 415 |
PNP | n.o. & n.c. | PSI 186 316 | PSI 186 416 |
|
|
|
---|
Nominal sensing distance: |
8 mm |
Effective sensing distance: |
6 - 10 mm |
Housing: |
M 18 |
Material: | nickel plated brass |
Mounting: |
non-flush |
Group: |
3 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 188 315 | PSI 188 415 |
PNP | n.o. & n.c. | PSI 188 316 | PSI 188 416 |
|
|
|
---|
Nominal sensing distance: |
10 mm |
Effective sensing distance: |
8 - 12 mm |
Housing: |
M 30 |
Material: | nickel plated brass |
Mounting: |
flush |
Group: |
4 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 306 315 | PSI 306 415 |
NPN | n.o. & n.c. | PSI 306 316 | PSI 306 416 |
|
|
|
---|
Nominal sensing distance: |
15 mm |
Effective sensing distance: |
12 - 15 mm |
Housing: |
M 30 |
Material: | nickel plated brass |
Mounting: |
non-flush |
Group: |
5 |
Dimensions: |
Cable version: | Connector version: |
| |
|
Output | Cable version | Connector version |
NPN | n.o. & n.c. | PSI 308 315 | PSI 308 415 |
PNP | n.o. & n.c. | PSI 308 316 | PSI 308 416 |
|
|
NPN n.o. (no) & n.c. (nc)
PNP n.o. (no) & n.c. (nc)
BR - brown, S - black, W - white, BL - blue
|
|